Cyclone
Ten megawatts, ready for the 33 kV grid.
- 20.26 MWh
- per block
- 10 MW
- at 33 kV
- <200 ms
- 0–100% ramp
Inside Cyclone
Scroll to open the block.
Four containers, one block
Each with its own PCS and transformer skid.
Straight onto 33 kV
Four 2.75 MVA transformers and one ring main unit.
Liquid-cooled LFP
80 racks, 20,160 cells, one plant controller.
Grid scale
Four Monsoon containers engineered as one 10 MW / 20 MWh block, scaling to half a gigawatt.
Scroll to look inside
Ten megawatts at a time.
Models
Cyclone 20
10 MW
20.26 MWh
~2 h · 33 kV block
Cyclone Specs
- Grid output
- 10,000 kW at 33 kV · ±2 MVAr
- Energy
- 20,257 kWh · 18.23 MWh usable (90% DoD)
- Batteries
- 80 racks · 20,160 LFP cells
- Power conversion
- 80 × 125 kW PCS in 8 × 1.25 MW cabinets
- Transformers
- 4 × 2.75 MVA Dyn11
- Switchgear
- 33 kV RMU 630 / 1250 A, 25 kA 3 s
- Round-trip efficiency
- 88% at 33 kV
- Response
- Full reversal <100 ms · 0–100% ramp <200 ms
- Auxiliary load
- 1.5 – 2.5%
- Footprint
- ~1,125 m² (45 × 25 m)
- Controls
- IEC 61850 · Modbus TCP · plant-level supervisory switching
- Scale
- Up to 500 MW / 1.01 GWh plant configuration
Nameplate values. Certifications, warranty and site design are confirmed in each quote.
Beaufort EMS
Decides every charge and discharge — peak shaving, ToU shifting, solar self-use and backup reserve — across one site or a fleet.
Anemo BMS
Three-tier supervision — cell, pack, rack — watching every cell, every second.
Jetstream PCS
Bidirectional 125 kW power modules that stack from a single cabinet to a 10 MW block.